7.1  General Requirements

 The dimensions of the Spa Suite shall be such to accommodate a minimum of [10 people] and a maximum of [20 people] at the same time and shall be in accordance with Guidance.

 If the Spa is on deck level it shall incorporate recessed steps and a hand rail.

 The Spa shall be separated visually and acoustically from the Main Pool to allow for relaxation, which requires quiet or privacy.

 Spa water temperatures and lighting should be in accordance with [national guidelines]2, and as stated in the Zone Data Sheets.

 Sauna and Steam temperatures and lighting should be in accordance with [national guidelines].

 Disability Wet Side Change Areas shall have access to the Spa Suite areas.

 A timer shall be fitted to the Spa in accordance with Guidance.

 Showers in the Wet Side Change Area shall be located near the Spa Suite.

 Drinking water shall be provided near the Spa Suite areas.

 Signage on safety issues should be located next to the Spa Suite areas.

 Secure pool stores shall be provided to accommodate the equipment necessary for Spa testing.

 Safety pulls should be installed next to the Spa, in the Steam and Sauna areas.



_________________________________________________________________________________
2 Is this Guidance or Legislation or something else?