10.3  Key Design Requirements

 Floor loadings should be calculated in accordance with the Sport England document "Fitness Suites and Aerobic Studios".

 A square or rectagonal design is preferred.

 There should be a minimum clear height of [3.5m (4.5m)].

 Clear aisles should be provided to ensure good access to all equipment for users of all abilities, and compliance with Legislation and Guidance relevant to the means of escape.

 The Fitness Suite shall meet the requirements of the Handbook of Sports and Recreational Building Design.

 A high quality sound and vision system shall be provided.

 The Fitness Suite shall include an assessment/consultation area/room.

 [] water fountains shall be provided in optimum locations.

 Any change in floor level should comply with DDA legislation guidance and the Sport England Guidance note "Access for Disabled Users".

 Induction loop that complies with BS EN 60118-4 and BS7594

 The Fitness Suite shall incorporate external views or views over other activity areas.

 Temperature cooling should be supplied to comply with the requirements of the Zone Data Sheets.