Utilities Services
Element | Requirement |
General | • Utilities Services should be free from leaks; and • Utilities Services should be maintained to deliver their specified capacity in compliance with the Facilities Requirements. |
Water Systems a) hot water systems; and | • continuously deliver water at the temperatures, quality criteria and flow rates defined in the Facilities Requirements; • taps valves and other related fittings and fixtures function in compliance with the Facilities Requirements; • all pipework and fittings shall be fastened securely to their intended points of anchorage; • no drips or leaks of water from pipework taps valves and/or fittings; • no leakage of waste and/or foul water and/or rain water; • adequately insulated to minimise risk of bursts and/or collapse due to cold weather; and • provide a safe and comfortable environment to Users. |
b) Cold water systems. | • continuous potable supply of water to all sanitary and domestic taps; • there shall be no drips or leaks of water from pipework taps and valves; and • adequately insulated to minimise risk of bursts and or collapse due to cold weather. |
Heating Services • humidifiers heaters; • ductwork; • inlet/outlet grilles; • cooling towers; • boilers; and • heat exchangers pumps. | • all heating services shall function as intended at the correct temperatures pressures and flow rates, voltages and frequency, quality and standards without undue noise or vibration; • heating system shall be independently controlled and tamper proof; • ductwork fittings and pipework shall be securely fastened to their intended points of anchorage; • pipework for space hearting shall be separate and dedicated to delivering heating only; • there shall be no leaks of water (or other heating cooling medium) or air from ventilation systems; • secure with authorised access only; and • free from corrosion and organic growth. |
Ventilation Services | • air changes and ventilation levels as required to achieve the Availability Requirements; • grilles are secured to points of anchorage and free from defects; • grilles and vents are free from dirt and dust; and • where installed extractor fans shall be checked to ensure device is securely installed and all fittings and controls are in place and operational complete with any safety mechanisms. |
Electrical Services • power supply; and • lighting. | • fuse elements or circuit breaker mechanisms in working order; • no signs of excessive heating; • standby emergency power source shall be operational secure and tested regularly; • emergency lighting units to comply with BS5299 or equivalent, be free from dust operational and be fully charged; • batteries and battery rooms shall be adequately ventilated free from acid leakage; batteries shall be topped up and fully charged; • electrical installations to comply with BS 7671 or equivalent; • shall be suitable for the environment in which installed; • lightning conductor should be complete, isolated and comply with BS 6651 or equivalent; • light environment shall comply with CIBSE design recommendations; and • security and access requirements shall comply with NACOSS standards. |
Gas Services | • gas systems are operated and maintained in accordance with current Gas Safety (Installation and Use) Regulations 1998; • all inspections and maintenance are carried out by a competent person; • all respective safety notifications and precautions are made and taken before commencement of any maintenance work; and • all inspections are complete with requisite Safety Certificates. |
Access Door Access Systems | • door entry systems are installed appropriately and secured to anchorage points complete with speaker phone systems from reception and other access control points shall be maintained in working order; and |
ramps | • all walkways paths ramps to and from the Facility and any part of it shall be maintained free from debris uneven surfaces and complete with associated rail supports for Users. |