Mechanical & Electrical Systems
Element | Requirement |
Generators and emergency power supply | • standby power source shall be operational, secure and tested regularly; • emergency lighting units shall comply with BS5299 or equivalent, be free from dust, operational and fully charged; • batteries and battery rooms shall be adequately ventilated, free from acid leakage; batteries shall be topped up and fully charged]; and • static inverters shall be in working order and not overheat during normal operational loading. |
Medium voltage distribution system • distribution equipment and protective devices fuse switches, isolators, distribution boards, fuses, MCBs, ACB, ELCBs and RCDs, and exposed distribution cables | • ratings shall be clearly marked; • fuse elements or circuit breaker mechanisms in working order; • contacts and connections clean and mechanically tight; • no overheating during normal operating loads; • secure to authorised access only; • recording instruments operational where necessary; • cable joint boxes free from compound leaks; and • marker and covering notices where necessary. |
High voltage distribution systems • distribution equipment, protective devices, isolators, distribution units, OCBs, ACBs and ELCBs | • ratings shall be clearly marked; • fuse elements or circuit breaker mechanisms in working order; • contacts and connections clean and mechanically tight; • no overheating during normal operating loads; • secure to authorised access only; • recording instruments operational where necessary; • transformers are free from oil leaks; • protective coatings are intact; • no signs of excessive heating; • electric strength of oil satisfactory; • cable joint boxes free from compound leaks; and • marker and covering notices where necessary. |
Hot & cold water systems | • deliver water at the temperatures and flow rates defined in the construction requirements without undue noise and vibration; • taps, valves and other related fittings and fixtures function as intended; • pipework and fittings shall be fastened securely to their intended points of anchorage; and • there shall be no drips or leaks of water from pipework, taps, valves and/or fittings. |
Heating, air conditioning and mechanical ventilation systems • boilers, calorifiers and heat exchangers; • fume cupboards; • humidifiers; • heaters; • ductwork; • mixing boxes and dampers; • coolers; • inlet/outlet grilles; • refrigeration equipment; • cooling towers; and • and other local ventilation systems. | • all ventilation systems shall function as intended without undue noise or vibration; • air changes and ventilation levels as required to achieve the construction requirements; • ductwork, fittings and pipework shall be securely fastened to their intended points of anchorage; • there shall be no leaks of water (or other heating/cooling medium) or air from ventilation systems; • secure to authorised access only; • free from corrosion, erosion and organic growth; and • all pipework and fittings to be clearly labelled to identify its service. |
Electrical power and other cabled systems Including24: • IT; • lighting; • communications; • safety; and • alarm systems. | • all electrical installations to comply with BS7671 or equivalent. • weatherproof where appropriate; • function as intended without undue noise or vibration; • wiring, fittings, fixtures, controls and safety devices shall be properly housed and fastened securely to their intended point of anchorage25 and labelled; • lighting conductor should be complete, isolated and comply with BS6651 or equivalent; • MICC cable protective coatings intact; and • light emittance within design Lux levels. |
Public health and other drainage systems • all sanitary ware and associated fittings). | • shall function as intended, without undue noise and vibration; • provide a safe and comfortable environment; • all pipework and fittings fastened securely to their intended points of anchorage; and • there shall be no leakage of waste and/or foul water and/or rain water. |
Fire fighting equipment | • fire extinguishers and other fire fighting equipment shall be maintained in accordance with BS 5306 Part 3 Code of Practice or equivalent; • sound, secure and fixed to their intended points of anchorage; • fully operational within manufacturer's recommendations; • hydrants, sprinklers and hoses shall be at correct operating pressure and capacity; • pipework shall be free from corrosion, leaks and drips; and • be of suitable type and quantity for the hazards present within their vicinity. |
Lifts | • shall function as intended without undue noise or vibration; • shall have a fully functioning control panel and phone; and • no persons shall be trapped in a lift for more than [30] minutes. |
_________________________________________________________________________________
24 Authority to specify on project specific basis
25 Safety devices shall be deemed to include all Un-interruptible Power Supplies (UPS) and power surge devices specified to protect personnel and equipment.